Ammonium nitrate storage in the US is governed by 29 CFR 1910.109(i) and, where locally adopted, NFPA 400. Anhydrous ammonia storage is governed by 29 CFR 1910.111 and, above a quantity threshold, OSHA’s Process Safety Management standard and EPA’s Risk Management Program. A fourth layer once added security screening, CFATS, but it has had no statutory authority since July 2023. None of these frameworks fully substitutes for another, and a facility handling both chemicals answers to several at once, each with its own thresholds and exemptions. India separates ammonium nitrate licensing from pressure-vessel licensing under two different rule sets; GCC operators work through civil defense and environmental permitting whose relationship to international codes is set by specific permit conditions rather than one regional rule. The priority for compliance staff is knowing which framework governs which chemical, and where each one’s authority currently stands.
What Governs This Area, and Where CFATS Currently Stands
Ammonium nitrate storage is governed by 29 CFR 1910.109(i) and NFPA 400 where adopted; anhydrous ammonia storage by 29 CFR 1910.111, and above 10,000 pounds in a covered process, by PSM and RMP. CFATS, a federal security-screening program, is not currently in force.
CFATS, the Chemical Facility Anti-Terrorism Standards program administered by CISA, lost its statutory authority when Congress let it lapse on July 28, 2023. CISA cannot currently require Top-Screen submissions, site security plans, or inspections. A September 2026 GAO report found a specific resulting gap still unresolved: facilities can no longer have personnel vetted against the federal terrorist watchlist through the program.<sup>1</sup> OSHA and EPA’s chemical-specific standards are unaffected by the lapse and remain fully enforceable. Separately, the Fertilizer Institute’s Responsible Ag and the International Fertilizer Association’s Protect & Sustain are voluntary stewardship certifications covering handling and storage practices; they demonstrate commitment beyond the regulatory floor but do not satisfy PSM, RMP, or storage-code obligations.<sup>2</sup>
The 2013 West, Texas explosion is the reference incident for this framework. The CSB’s final report documents that West Fertilizer stored fertilizer-grade ammonium nitrate in wooden bins that were not treated against impregnation, as 1910.109(i)(4)(ii)(b) independently requires; OSHA cited the facility for exactly this after the explosion, a federal requirement that applies regardless of whether a local fire code has been adopted.<sup>3</sup> Separately, the facility operated under PSM’s retail exemption, which is relevant to the ammonia on site, not the ammonium nitrate; ammonium nitrate has never been a PSM-listed chemical at all, so its absence from PSM coverage is a different fact from the retail exemption and the two should not be merged into one explanation. The CSB’s recommendations covered both: physical storage construction, emergency-responder training, and the standards-coverage gaps between agencies.
Scope and Applicability
Applicability depends on the chemical, its concentration and quantity, and the facility’s classification. 1910.109(i) applies to ammonium nitrate at 60 percent concentration or more and 1,000 pounds or more; PSM applies to anhydrous ammonia at or above 10,000 pounds in a covered process (via Appendix A, where ammonia carries its own listed threshold), and RMP applies above that same quantity, counted at the process level rather than as a site-wide total.<sup>4</sup>

The PSM retail exemption is the key applicability question for US facilities. OSHA’s April 30, 2018 memorandum is an enforcement policy, not a regulatory redefinition: it states OSHA will not issue PSM citations to employers in three specific NAICS classifications (grain and field bean merchant wholesalers, other farm product raw material merchant wholesalers, and farm supplies merchant wholesalers), following the D.C. Circuit’s 2016 decision vacating OSHA’s earlier attempt to narrow the exemption by memo rather than rulemaking.<sup>5</sup> The underlying regulatory exemption in 1910.119(a)(2)(i) still does not define “retail facility” in the rule itself; the 2018 memo is current enforcement guidance built on that gap, and it is explicit that exempt facilities still must comply with 1910.109(i) and 1910.111. West Fertilizer fell under this enforcement policy for its ammonia and was separately cited for ammonium nitrate storage deficiencies unrelated to that exemption.
Recognized for excellence.
PROJECTS DELIVERED ACROSS THE GLOBE
Key Requirements by Framework
1910.111: Storage and Handling of Anhydrous Ammonia
1910.111 governs the design, construction, and location of anhydrous ammonia systems, including refrigerated storage, independent of whether PSM applies. It sets requirements for container design and marking, safety relief valves, and system labeling, and it applies to ammonia manufacturing and refrigeration facilities as well as fertilizer sites. A facility exempt from PSM through the retail enforcement policy is not exempt from 1910.111; the two operate on separate tracks.
OSHA Process Safety Management (29 CFR 1910.119)
PSM requires fourteen documented elements for a covered process, triggered for ammonia at or above its 10,000-pound Appendix A threshold. The 2018 retail enforcement policy removes this requirement for the three listed NAICS classifications regardless of quantity; a non-retail facility gets no such exemption.
NFPA 400 Chapter 11: Ammonium Nitrate
NFPA 400, now in its 2025 edition, consolidates ammonium nitrate provisions previously issued as the separate NFPA 490. It sets separation distances, NFPA 704 placarding, and bin-construction guidance, with the 2019 edition adding retroactivity language after the West investigation. Its applicability at a given site depends entirely on which edition, if any, the local jurisdiction has adopted; the code carries no independent federal force. The specific clause-level requirements below the 60 percent concentration threshold, including definitions and exclusions, should be confirmed against the current chapter text rather than assumed from a publisher’s summary.
EPA Risk Management Program
RMP applies above 10,000 pounds of ammonia in a covered process, but the obligation differs by program level (1, 2, or 3) and by response posture. A “responding” facility, which commits its own trained personnel to react to a release, must develop and implement an emergency response program under 40 CFR 68.95. A “non-responding” facility, which relies on local responders instead, still has obligations: notification mechanisms, annual coordination meetings with local responders, and annual notification exercises, alongside an Emergency Action Plan rather than a full Emergency Response Plan.<sup>6</sup>
CFATS
Included for completeness only: with no statutory authority since July 28, 2023, CFATS currently imposes no screening, reporting, or inspection obligation on any facility.
| Framework | Legal Status (Oct 2026) | Chemical | Threshold | Core Requirement |
| 1910.111 | Active federal regulation | Anhydrous ammonia | No quantity threshold | System design, construction, labeling |
| PSM (1910.119) | Active; retail-exempt for 3 NAICS codes | Anhydrous ammonia | At or above 10,000 lb (process) | 14-element process safety program |
| 1910.109(i) | Active federal regulation | Ammonium nitrate | 60% concentration AND 1,000 lb+ | Storage, segregation, construction |
| NFPA 400 Ch. 11 (2025) | Enforceable only where locally adopted | Ammonium nitrate | 60%+ concentration | Separation, placarding, construction (verify current clauses) |
| EPA RMP | Active; tiered, responder-status dependent | Anhydrous ammonia | Above 10,000 lb (process) | Prevention program; ERP or EAP + exercises |
| CFATS | Lapsed since July 28, 2023 | Ammonium nitrate | N/A | None currently enforceable |
Compliance in India and the GCC

India licenses ammonium nitrate manufacture, possession, and transport through the Ammonium Nitrate Rules, 2012, and licenses pressure vessels separately through the Static and Mobile Pressure Vessels (Unfired) Rules, 2016; both are administered by PESO but are not interchangeable. Forms A-1 through A-5 under the Ammonium Nitrate Rules are application forms; the license itself is issued on a separate P-series form (manufacturing, for example, on Form P-1).<sup>7</sup> Whether SMPV(U) covers a specific ammonia storage configuration, including atmospheric refrigerated tanks, depends on that rule’s own vessel definitions and exclusions and should be confirmed case by case rather than assumed. On fire safety, IS 15394:2003, “Fire Safety in Petroleum Refineries and Fertilizer Plants,” published by the Bureau of Indian Standards, covers layout and fire protection for this sector specifically.<sup>8</sup> OISD-117 and OISD-118 are oil-and-gas-sector codes (petroleum depot fire protection and installation layout, respectively), not dedicated ammonia standards, though large integrated complexes sometimes reference their layout principles by extension.
In Qatar, Civil Defence guidance sets out specific NFPA-based compliance conditions for covered facility types as part of its permitting process.<sup>9</sup> This is a single, sourced example rather than a regional generalization; how other GCC states handle the same question would need country-specific verification before extending the pattern. Environmental permitting authorities separately set emission limits for ammonia and nitrogen compounds. Multinational operators commonly use the World Bank/IFC Environmental, Health, and Safety Guidelines for Nitrogenous Fertilizer Production as a technical reference where local codes are silent on a design parameter; it applies through World Bank Group project finance policy, not as domestic law, and does not replace the country-specific permit a project still needs.<sup>10</sup>
Implementation Checklist
| Step | Action | Evidence Required | Owner | Status |
| 1 | Inventory ammonia and ammonium nitrate by process | Process flow data, storage records | Process engineering | |
| 2 | Map each quantity against 1910.111, PSM, RMP, 1910.109(i), and the relevant India/GCC instrument | Threshold and applicability memo | Compliance | |
| 3 | Confirm PSM retail enforcement-policy status and what still applies regardless | NAICS classification, legal review | Compliance / legal | |
| 4 | Confirm wooden-bin impregnation protection and ammonium nitrate storage construction against 1910.109(i), independent of local code adoption | Site inspection, material treatment records | Fire protection / EHS | |
| 5 | Confirm NFPA edition adopted locally, if any, and its retroactivity provisions | AHJ confirmation | Fire protection engineering | |
| 6 | Reconcile management-of-change and training documentation with as-built and as-trained conditions | MOC log, training audit | EHS | |
| 7 | Prioritize corrective actions by whether each is a statutory violation or a best-practice gap | Risk ranking, corrective action tracker | Plant management |
We are a global authority in process safety and risk engineering, and engineering support for applicability review and gap closure is available through iFluids’ engineering design and consulting services.
Conclusion
Ammonia and ammonium nitrate storage compliance runs through several independent frameworks rather than one rulebook: PSM and RMP for ammonia above threshold, 1910.109(i) and locally-adopted NFPA 400 for ammonium nitrate, and 1910.111 for ammonia regardless of PSM status. The PSM retail enforcement policy affects only the PSM requirement, not the chemical-specific storage standards. CFATS has had no statutory authority since 2023. India separates ammonium nitrate licensing from pressure-vessel licensing under two PESO rule sets, and Qatar’s civil defense permitting makes specific NFPA references binding by condition, a pattern that should be verified rather than assumed elsewhere in the GCC. Speak with our process safety team to scope a facility-specific applicability review, or browse related standards articles and case studies.
Frequently Asked Questions
No. Ammonium nitrate has never been a PSM-listed chemical, so PSM does not apply to it regardless of quantity. It is governed instead by 1910.109(i) and, where adopted, NFPA 400. Anhydrous ammonia at the same site can trigger PSM independently, subject to the retail enforcement policy.
OSHA’s 2018 memo is enforcement policy stating OSHA will not cite three specific NAICS classifications for PSM, following a D.C. Circuit ruling against an earlier, narrower OSHA interpretation. It does not remove 1910.109(i) or 1910.111 obligations, only the PSM program requirement for those classifications.
OSHA permits wooden bins for ammonium nitrate only if treated against impregnation under 1910.109(i)(4)(ii)(b). West Fertilizer was cited for untreated bins after the explosion; this is an independent federal requirement that applies regardless of whether the local jurisdiction has adopted NFPA 400.
No. Its statutory authority lapsed July 28, 2023, and a September 2026 GAO report found the resulting personnel-vetting gap unresolved. Confirm current status before treating any CFATS obligation as active.
No. Requirements scale by program level, and a “responding” facility needs a full emergency response program while a “non-responding” facility needs an Emergency Action Plan, notification mechanisms, and annual coordination and exercises with local responders instead.
No. They are oil-and-gas-sector codes for petroleum depot fire protection and installation layout. Ammonia and ammonium nitrate in Indian fertilizer plants are governed instead by the SMPV(U) Rules 2016, the Ammonium Nitrate Rules 2012, and IS 15394:2003.