Vedanta Limited – Cairn Oil & Gas operates the Rajasthan Block, which includes the Mangala, Aishwariya, Bhagyam, Shakti, Kaameshwari West and several marginal and satellite fields.Crude oil produced from these fields is processed through the Mangala Processing Terminal (MPT), an onshore oil and gas processing facility that acts as a central gathering and processing point for production from the Rajasthan Block.
As operating conditions and crude characteristics change, the original fire protection design basis may also need to be reviewed. iFluids Engineering was engaged to carry out a Fire Safety Adequacy Study for the Mangala Processing Terminal and associated crude oil pipeline and terminal facilities. The purpose was to determine whether the existing active fire protection, passive fire protection, firewater infrastructure, emergency systems and equipment protection measures remained suitable for the revised fire hazard.

Project Background
The Mangala Processing Terminal forms part of an integrated oil production, processing and transportation system. Hydrocarbons produced from the Rajasthan fields are processed at the terminal before being transported through the associated crude oil pipeline network and downstream terminal facilities.
The scope of work of iFluids Engineering is limited to the different components associated with Mangala Terminal facility.
- Mangala Processing Terminal
- Unloading Bay near MWP-08.
- Crude Oil Pipeline from MPT to AGI-5
- Crude Oil Pipeline from AGI 5 to Bhogat.
- Radhanpur Terminal
- Viramgam Terminal
- Bhogat Terminal and SPM
These facilities perform different operating functions and therefore present different fire hazards. A process area containing pressurised hydrocarbon equipment, for example, cannot be assessed in exactly the same manner as a terminal or pipeline installation. The study therefore considered the individual function, operating condition and credible fire scenarios associated with each part of the system.
Scope of the Fire Safety Adequacy Study
The assessment covered the main protection layers associated with the facilities. This included the active fire protection system, passive fire protection arrangements, equipment material adequacy, fire hazard and consequence assessment, and the adequacy of emergency breathing apparatus and communication systems.
Rather than assessing these items independently, the study considered how they would work together during a credible fire event. This is particularly important in hydrocarbon facilities, where the failure or limitation of one protection system can increase the demand on another.
Recognized for excellence.
PROJECTS DELIVERED ACROSS THE GLOBE
1. Active Fire Protection System
The Fire Safety Adequacy Study reviewed the existing active fire protection system, including firewater storage, pumps, distribution networks, hydrants, monitors and fixed water spray systems. The assessment checked whether the firewater system could provide adequate flow and pressure for credible emergency scenarios.

2. Passive Fire Protection System
The passive fire protection assessment covered equipment spacing, bunds, dykes, containment and structural fireproofing. The study also reviewed whether critical equipment exposed to thermal radiation required additional protection to reduce the potential for fire escalation.

3. Equipment Material Adequacy
The study reviewed equipment and supporting structures for material suitability, structural integrity and heat exposure. Particular attention was given to safety-critical equipment that must remain functional during a fire or emergency shutdown condition.
4.Fire Hazard Analysis and Consequence Modelling
The fire hazard analysis considered credible pool fire, jet fire and flash fire scenarios. Fire consequence modelling was used to assess thermal radiation, equipment exposure, escalation potential and impacts on personnel and evacuation routes.
–Fire Escalation Assessment
The study evaluated whether thermal radiation from an initial fire could affect nearby equipment and lead to a larger incident. Equipment spacing, isolation, fireproofing and fixed firefighting systems were reviewed as part of the fire escalation assessment.
–Fire and Gas Detection
The existing fire and gas detection system was reviewed to determine whether credible hazards could be detected early enough to initiate alarm, shutdown and emergency-response actions.
5. Emergency Breathing Apparatus and Communication Systems
The study reviewed the adequacy of emergency breathing apparatus and communication systems.
Emergency communication should allow personnel to raise alarms, coordinate firefighting, issue evacuation instructions and support emergency-response teams. Breathing apparatus provisions should also match the hazards that responders may encounter.

Codes and Standards Referred for the Study
| Code / Standard | Application |
| OISD-STD-117 | Fire protection facilities for terminals, pipeline installations, lube oil installations and petroleum depots |
| OISD-STD-118 | Layouts for oil and gas installations |
| OISD-STD-189 | Fire protection provisions for onshore drilling, workover and production installations |
| OISD-STD-173 | Fire prevention and protection for electrical installations |
| OISD-STD-163 | Process control room safety |
| OISD-STD-164 | Fireproofing of steel supporting structures |
| OISD-STD-244 | Storage and handling of petroleum products at depots and terminals |
| NFPA 2001 | Clean-agent fire-extinguishing systems |
| NFPA 15 | Fixed water spray fire protection systems |
| NFPA 20 | Stationary fire pumps |
| NFPA 30 | Flammable and combustible liquids |
| NFPA 72 | Fire alarm and signalling systems |
| API 2218 | Fireproofing practices for petroleum and petrochemical facilities |
| Petroleum Rules | Applicable petroleum storage and handling requirements |
| CEA Regulations | Applicable electrical safety requirements |
Applicability depends on facility type, project requirements, statutory jurisdiction and the approved design basis. We do not apply a standard simply because it appears on a generic checklist.
Main Objectives of the Study
The overall objective was to determine whether the process and fire protection systems remained adequate following the change in crude-oil flash point.The work combined fire-hazard identification, consequence modelling and protection-system assessment. It examined flash-fire, jet-fire and pool-fire scenarios and evaluated their potential heat-radiation effects.
The study also considered fire escalation, equipment inter-separation and the exposure of critical equipment.Where equipment or supporting structures could be affected, the requirement for fireproofing or additional protection was reviewed.
Another major part of the study involved the existing firewater system. Firewater pump capacity, header sizing, storage, hydrants and monitors were assessed against the revised fire-protection basis.Escape routes and evacuation arrangements were also reviewed to confirm that personnel-protection measures were considered alongside equipment protection.

Conclusion
The Fire Safety Adequacy Study for Mangala Processing Terminal of Vedanta demonstrates why existing fire protection systems should be reviewed when hydrocarbon properties or operating conditions change. The change in crude-oil flash point required more than an inspection of installed firefighting equipment. It required assessment of credible fire hazards, consequence effects and the ability of existing protection systems to respond.
By combining fire consequence modelling with firewater adequacy, passive fire protection, equipment exposure, drainage, detection, emergency response and evacuation review, iFluids Engineering provided an integrated assessment of the facility’s fire-safety basis. For refineries, processing facilities, tank farms, terminals and pipeline installations, this type of study helps identify whether existing safeguards remain suitable and where engineering improvements may be required.
Frequently Asked Questions
A Fire Safety Adequacy Study evaluates whether the existing fire prevention, detection, firefighting, passive protection and emergency-response systems at a facility are suitable for the actual fire hazards present.
A change in flash point can alter the fire-hazard classification of the crude and may affect fire scenarios, firewater requirements, equipment separation, containment and emergency-response provisions. The existing protection basis should therefore be reassessed.
The assessment typically considers firewater storage, pump capacity, distribution headers, network performance, hydrants, monitors and fixed protection systems to determine whether the required flow and pressure can be supplied.
Depending on the process and release conditions, representative scenarios can include pool fire, jet fire and flash fire. The scenarios should be selected based on credible facility hazards rather than using a generic list.
No, Compliance is one part of the study. The wider purpose is to determine whether the actual protection systems can respond effectively to credible fire scenarios and whether improvements are required to reduce escalation and protect personnel and equipment.
Changes in crude properties, production rates, equipment configuration or plant layout can alter the basis on which an existing fire protection system was originally designed. iFluids Engineering supports refineries, oil and gas processing plants, terminals, tank farms and pipeline facilities with Fire Safety Adequacy Studies, firewater hydraulic assessments, fire consequence modelling, active fire protection assessments and passive fire protection studies. Our approach considers the actual facility hazard and how the existing protection layers work together during an emergency.